Product overview
Santak 3C3 HD series UPS (20~200kVA) is listed by Iwell for online UPS enquiries. The published specifications include Power range: 20–200 kVA / 20–200 kW. Compare both VA and W ratings, input/output voltage, connections and installation space. Specify the actual load and desired backup time when reviewing battery options.
Features
- Adopt the new generation of IGBT and optimized three-level inverter topology, with online efficiency up to 96% and ESS mode efficiency up to 99%
- Output power factor 1.0
- Internal modular design, MTTR<30 minutes
- High power density, save more than 50% footprint
- Intelligent battery management function to extend battery life cycle
- 5" color touch screen for easy operation
- Support lead-acid batteries and lithium batteries
- Parallel UPS units up to 4, support common battery @2 UPS parallel
- Support battery cold start
Santak 3C3 HD selection and documents
Compare both VA and W ratings, input/output voltage, connections and installation space. Specify the actual load and desired backup time when reviewing battery options.
Use the specification table below and the Documents tab to review 3C3 HD. Match the exact model or series configuration before ordering. Read the selection guidance.
Compare online UPS products or browse Santak product families. For a quotation, provide the complete model, quantity, destination and required configuration.
Technical specifications
| Parameter | 20 kVA / 20 kW | 30 kVA / 30 kW | 40 kVA / 40 kW | 60 kVA / 60 kW | 80 kVA / 80 kW | 100 kVA / 100 kW | 120 kVA / 120 kW | 160 kVA / 160 kW | 200 kVA / 200 kW |
|---|---|---|---|---|---|---|---|---|---|
| Input — Wiring | Three phase + Neutral + Ground | ||||||||
| Input — Mains voltage range | 201–478 Vac (L-L); 116–276 Vac (L-N) | ||||||||
| Input — Bypass voltage range | 338–458 Vac (L-L); 195–264 Vac (L-N) | ||||||||
| Input — Frequency | 50/60 Hz | ||||||||
| Input — Frequency range | 40–72 Hz | ||||||||
| Input — Power factor | ≥0.99 | ||||||||
| Input — THDi | <2% linear load; <5% non-linear load | <2% linear load; <5% non-linear load | <2% linear load; <5% non-linear load | <2% linear load; <5% non-linear load | <2% linear load; <5% non-linear load | <3% linear load; <5% non-linear load | <3% linear load; <5% non-linear load | <3% linear load; <5% non-linear load | <3% linear load; <5% non-linear load |
| Output — Voltage | 230/400 Vac default (220/380 V, 240/415 V optional) | ||||||||
| Output — Voltage regulation | <1% @ steady state | ||||||||
| Output — Power factor | 1 | ||||||||
| Output — Overload | 102–110%: 60 mins; 111–125%: 10 mins; 126–150%: 1 min | ||||||||
| Output — Parallel | Up to 4 units | ||||||||
| Efficiency — Online mode | Up to 96% | ||||||||
| Efficiency — ECO mode | Up to 99% | ||||||||
| Battery — Voltage | 320–607 V (432 V default) | ||||||||
| Battery — Max. charge current | 25 A | 38 A | 50 A | 76 A | 100 A | 100 A | 120 A | 160 A | 200 A |
| Environment — Ambient temperature | 0–40°C | ||||||||
| Environment — Storage temperature | −15 to +55°C | ||||||||
| Environment — Ambient humidity | 5–95% | ||||||||
| Environment — Altitude, no derating | <1000 m | ||||||||
| Physical — Dimensions (W×D×H) | 330×668×521 mm | 330×668×521 mm | 330×668×521 mm | 330×690×975 mm | 330×690×975 mm | 500×850×1230 | 500×850×1230 | 550×850×1600 | 550×850×1600 |
| Physical — Net weight | 41 kg | 45 kg | 45 kg | 90 kg | 90 kg | 149 kg | 149 kg | 245 kg | 270 kg |
| Physical — Gross weight | 50 kg | 55 kg | 55 kg | 131 kg | 131 kg | 162 kg | 162 kg | 270 kg | 295 kg |
| Quality — Safety | IEC/62040 | ||||||||