Product overview
Santak 3C3 HD series UPS (300~600kVA) is listed by Iwell for online UPS enquiries. The published specifications include Series range: 300–600 kVA. Compare both VA and W ratings, input/output voltage, connections and installation space. Specify the actual load and desired backup time when reviewing battery options.
Features
- Adopt the new generation of IGBT and optimized three-level inverter topology, with online efficiency up to 97% and ESS mode efficiency up to 99%
- Output power factor 1.0
- Internal modular design, MTTR<30 minutes
- Intelligent battery management function to extend battery life cycle
- 7" color touch screen for easy operation
- Support lead-acid batteries and lithium batteries,super capacitors and other DC energy storage systems
- Maximum charging current up to 400A, faster recovery of capacity
- Support 4 UPS parallel and share common battery
- Support battery cold start
- Intelligent dummy load test function
- With internal module redundancy function, higher reliability
- Adopt oil-filled capacitor, maintenance-free and long service
Santak 3C3 HD selection and documents
Compare both VA and W ratings, input/output voltage, connections and installation space. Specify the actual load and desired backup time when reviewing battery options.
Use the specification table below and the Documents tab to review 3C3 HD. Match the exact model or series configuration before ordering. Read the selection guidance.
Compare online UPS products or browse Santak product families. For a quotation, provide the complete model, quantity, destination and required configuration.
Technical specifications
| Parameter | 400 kVA / 400 kW | 500 kVA / 500 kW | 600 kVA / 600 kW |
|---|---|---|---|
| Input — Wiring | Three phase + Neutral + Ground | ||
| Input — Voltage range | 240–478 Vac / 138–276 Vac | ||
| Input — Bypass voltage range | 340–438 Vac / 196–253 Vac | ||
| Input — Frequency | 50/60 Hz | ||
| Input — Frequency range | 40–72 Hz | ||
| Input — Power factor | ≥0.99 | ||
| Input — THDI | <3% @ full linear load | ||
| Output — Voltage | 230/400 Vac (220/380, 240/415 optional) | ||
| Output — Frequency | 50 Hz / 60 Hz | ||
| Output — Power factor | 1 | ||
| Output — THDV | <1% @ full linear load | ||
| Output — Overload | 10mins@111–125%, 1min@126 | ||
| Output — Parallel | 4 units | ||
| Efficiency — Double conversion mode | Up to 97% | ||
| Efficiency — ESS mode | Up to 99% | ||
| Battery — Type | VRLA, NiCad, Lithium battery | ||
| Battery — Voltage | 480 V (40 pcs)–690 V (50 pcs), default 480 V | ||
| Battery — Charge current (max.) | 280 A | 320 A | 400 A |
| Environment — Ambient temperature | 0–40°C | ||
| Environment — Storage temperature | −15 to +55°C | ||
| Environment — Ambient humidity | 5–95% | ||
| Environment — Altitude, no derating | <1000 m | ||
| Physical — Dimensions (W×D×H) | 1100×1000×2000 | ||
| Physical — Net weight | 650 kg | 700 kg | 820 kg |
| Physical — Gross weight | 770 kg | 820 kg | 940 kg |
| Quality — Safety | IEC/62040 | ||